| Technical data | AGS../.. | AMT-0-V |
| Max. system voltage: | 0,72 kV | 0,72 kV |
| Test voltage: | 3 kV | 3 kV |
| Nominal frequency: | 50 Hz | 50 Hz |
| Rated primary current In: | see on datasheets | see on datasheets |
| Nominal load capacity: | see on datasheets | see on datasheets |
| Nominal secondary current: | 1A or 5A | 1A or 5A |
| Rated short time current Ith: | 40 x In (1 s) | 60 x In (1 s) |
| Nominal surge current Idyn: | 2,5 x Ith | 2,5 x Ih |
| Rated continous thermal current: | 1,2 x In | 1,2 x In |
| Instrument security factor: | FS5, FS10 | FS5, FS10 |
| Temperature class: | B | B |
| Ambient temperature: | -25°C - 40°C | -25°C - 40°C |
| Storage temperature: | -40°C - 60°C | -40°C - 60°C |
| Protection degree (secondary clip cover): | IP20 | IP20 |
| Standards: | EN 61869-1; EN 61869-2 | EN 61869-1; EN 61869-2 |
| Flammibility: | UL94 V-0 | - |
| Compliant with RoHS directiven : | Yes | Yes |
| Fastening system (cable, busbar): | Yes | - |
| Fitted busbar, resin filled: | - | Yes |
| Data sheet: | Safety datasheet which leave „VOID” text after removal | Aluminium, riveted |